描述
它的输出接点之所以会出现外接K合闸而不能使之分闸的故障现象,是因为KD的动合触头在分断时出现粘合现象。动合触头被粘合,原因有二:(1)与之并联的RC支路元件可能损坏,或者断线,灭弧能力下降,使KD动合触头分断时可能被粘合住;(2)外接的K容量过大。因K容量大时,线圈中贮存的磁场能量就大,当超过PLC输出接点的分断能力时进行分断,PLC输出继电器的动合触头有可能被粘合住。